IEEE C37.94 Optical Modules
Improve Safety and Reliability of Intra-Substation Data Links
Low Speed (IEEE C37.94) Optical Modules
- 1-port and 4-port modules, both IEEE C37.94-compliant
- Hot-swappable
- One tri-color LED indicates status of each C37.94 port
- Green – SYNC
- Red – UNSYNC/LOS
- Yellow – Yellow Alarm
- Flashing Yellow – Loopback
Optical Characteristics
- Optical Fiber
- Multi-mode
- 62.5 μm core diameter optical cable
- 50 μm core diameter optical cable
- Optical Source: LED
- Optical Budget
- 9.6 db at 50 μm of core size
- 15 db at 62.5 μm of core size
- Connector: One pair of Tx/Rx ST-connectors per port
- Typical transmission distance: Maximum 2 km
- The center emission wavelength: 820 nm +/- 25 nm
Operating Modes
- Auto: System detects both Rx and Tx bandwidth by examining the content of the payload
- Manual: User-configurable Tx bandwidth
Test Patterns
- 2exp20-1 (QRSS)
Loopback Capabilities
- Line, Local, Payload
Communication Failure Scenarios
- LOS: Declared within 1 ms after receiving 2 or more errors in 8 consecutive framing patterns; cleared after receiving 8 consecutive correct framing patterns
- Yellow: Declared when 3 consecutive received frames have the “Yellow” bit set and there is no LOS; cleared after 3 consecutive received frames have the “Yellow” bit cleared or the LOS is present
- Framing and Payload Errors
Clocking Criteria
- Teleprotection equipment should use the signal from the multiplexer for clocking
- The multiplexer should not use the signal from the teleprotection equipment for clocking
Management
- Local access via RS232 serial interface
- Remote access via SNMP MIB and Node Viewer
Fault Management
- Support for TRAP PDUs
- Events and TRAPs generated for Port Alarm, Module Insertion/Removal, and Module Failure indications
Alarms
- Configurable levels (Critical, Major, Minor, Disable) for LOS, and YEL
- Alarms triggered based on error level thresholds set up for the ES, SES, and UAS
Performance Reports